Use external meter with 50 KW Inverter

Created by Gerrie Rautenbach, Modified on Sat, 20 Jul at 9:47 PM by Gerrie Rautenbach

50 KW Inverter Meter Port


Using the EASTRON external meter:


Using the EASTRON with CT's

This Eastron is sold with 150A:1A CT's

This Eastron can use CT's with a secondary current of 1A or 5A

This Eastron was tested with 1200A:5A CT's and functioned correctly.



Using the CHINT DTSU666 CT 250A/50mA


CHINT DTSU666 CT 250A/50mA operation work only with the CT version of this meter.


Using the CHINT with CT's




Using the ChiNT DTSU666 0.05-1.5(6)A is not recommended with CT

CHINT DTSU666 CT 0.05-1.5(6)A does NOT operate with the CT's via the RS485 Modbus


CHINT DTSU666 CT 0.05-1.5(6)A do operate if connected directly and using the meters internal CT's

The maximum current through the internal CT busbar is 80A per phase.



Was this article helpful?

That’s Great!

Thank you for your feedback

Sorry! We couldn't be helpful

Thank you for your feedback

Let us know how can we improve this article!

Select at least one of the reasons
CAPTCHA verification is required.

Feedback sent

We appreciate your effort and will try to fix the article