50 KW Inverter Meter Port
Using the EASTRON external meter:
Using the EASTRON with CT's
This Eastron is sold with 150A:1A CT's
This Eastron can use CT's with a secondary current of 1A or 5A
This Eastron was tested with 1200A:5A CT's and functioned correctly.
Using the CHINT DTSU666 CT 250A/50mA
CHINT DTSU666 CT 250A/50mA operation work only with the CT version of this meter.
Using the CHINT with CT's
Using the ChiNT DTSU666 0.05-1.5(6)A is not recommended with CT
CHINT DTSU666 CT 0.05-1.5(6)A does NOT operate with the CT's via the RS485 Modbus
CHINT DTSU666 CT 0.05-1.5(6)A do operate if connected directly and using the meters internal CT's
The maximum current through the internal CT busbar is 80A per phase.