Prior to reading this document, please familiarise yourself with the following documents Recommended External Meters and Eastron Meters: CT Selection and Settings to ensure that you have the correct meter.
Step 1: Wire Live into port 4 and Neutral into port 3.
Step 2: Connect the CT coil, wiring black into port 2 and white into port 1.
Step 3: Using a CAT-5 or CAT-6, use solid brown and brown/white or solid blue and blue/white (depending on the cable you use) and move the others away. Connect solid brown or blue (depending on the cable you use) to port 9 and brown/white or blue/white (depending on the cable you use) to port 10.
Step 4: On the other side of the CAT-5 or CAT-6, use a RJ45 connector and connect solid brown or blue (depending on the cable you use) into pin 4 and brown/white or blue/white (depending on the cable you use) into pin 5.
Please refer to the illustration below, which shows the pin-out configuration for your reference. Please note that this may vary according to the inverter model.
Step 5: Connect the RJ45 into the METER port or RS485 in case your inverter does not have this port.
Step 6: Go to "Advanced Settings" on the inverter screen and enable "External Meter for CT", after that select Eastron-1P on the "Meter Select" field.
Was this article helpful?
That’s Great!
Thank you for your feedback
Sorry! We couldn't be helpful
Thank you for your feedback
Feedback sent
We appreciate your effort and will try to fix the article