Single-Phase Eastron Meter with Single-Phase Inverter

Created by Gerrie Rautenbach, Modified on Thu, 26 Sep at 10:05 AM by Jorge Ruiz Padilla

Prior to reading this document, please familiarise yourself with the following documents Recommended External Meters and Eastron Meters: CT Selection and Settings to ensure that you have the correct meter.


Step 1: Wire Live into port 4 and Neutral into port 3.



Step 2: Connect the CT coil, wiring black into port 2 and white into port 1.




Step 3: Using a CAT-5 or CAT-6, use solid brown and brown/white or solid blue and blue/white (depending on the cable you use) and move the others away. Connect solid brown or blue (depending on the cable you use) to port 9 and brown/white or blue/white (depending on the cable you use) to port 10.



Step 4: On the other side of the CAT-5 or CAT-6, use a RJ45 connector and connect solid brown or blue (depending on the cable you use) into pin 4 and brown/white or blue/white (depending on the cable you use) into pin 5.




Please refer to the illustration below, which shows the pin-out configuration for your reference. Please note that this may vary according to the inverter model.



Step 5: Connect the RJ45 into the METER port or RS485 in case your inverter does not have this port.



Step 6: Go to "Advanced Settings" on the inverter screen and enable "External Meter for CT", after that select Eastron-1P on the "Meter Select" field.