Low Power Mode Daily Sequence

Created by Carol Hawes, Modified on Wed, 13 Mar 2024 at 12:02 PM by Carol Hawes

LOW POWER MODE DAILY SEQUENCE

 

If “Low Power Mode<Low Batt” is selected in Battery settings, the battery will go into hibernation when it discharges down to the “Low Batt(0-100%)” level also set in Battery settings.





The SOC% in “System Mode” under timer settings

 must be 1% below the “Low Batt” level set.

 




Recommended Settings:

Low battery 25%

Shutdown 20%

SOC/V 24%

 

 

 

 

 

 

 

 










When set up like this the daily sequence of events will be as follows:

  1. Solar starts up and when it reaches 125V on strings inverter starts up.
  2. When the batteries reach 30% charge from either PV or grid, they will start up.
  3. Batteries continue to charge/discharge, depending on System Mode settings.
  4. Solar stops and goes under 125V on strings, batteries continue to charge/discharge depending on System Mode settings.
  5. Battery reaches 25% (if this is low battery level set) and inverter and batteries go into hibernation until such time as solar starts up again.