Grid Connect and Disconnect Notifications UK
The issue 99% of the time is that the grid settings are set to the NI Standard and not the UK. NI has a lower grid voltage disconnect than the UK causing the grid relay to shut down. In the NI Standard these values are set to 253V or lower.
Please make sure the Grid Mode is set to "General Standard", settings under General Standard should be as follows: