Battery fuse rating per inverter

Created by Lee Dobson, Modified on Tue, 30 Jan 2024 at 04:50 PM by Lee Dobson

Kindly note the recommended battery fuse rating provided below. It is advisory in nature and not mandatory. Consider it as a guideline; however, lower-rated fuses may be utilized, ensuring that either the inverter's maximum charge current rating or the battery's maximum charge current is lower than the installed fuse. This approach serves to safeguard the inverter.


Inverter Size
Battery Connection
Phase
Inverter Max Charge Current (A)
Fuse Rating (A)
3.6kW
Parallel
1
90
120
5kW
Parallel
1
120
125
8kW
Parallel
1
190
200
8kW
Parallel
3
190
200
10kW
Parallel
3
210
220
12kW
Parallel
3
240
250
16kW
Parallel
1
290
310
50kW
Series
3
100
120

Was this article helpful?

That’s Great!

Thank you for your feedback

Sorry! We couldn't be helpful

Thank you for your feedback

Let us know how can we improve this article!

Select atleast one of the reasons
CAPTCHA verification is required.

Feedback sent

We appreciate your effort and will try to fix the article