On a three-phase inverter you have the ability to change the phase rotation of the system natively in the inverter settings between 0/120/240 (clockwise rotation) and 0/240/120 (anti-clockwise rotation).
On the single-phase inverter this is not a built in setting. So when installing 3 single-phase inverters across three-phases you have to perform a workaround to clear the W03 alarm.
For a usual setup on a system with 3 singe-phase units on a three-phase system the parallel settings should be as below:
| A | B | C |
Parallel | Yes | Yes | Yes |
Master or Slave | Master | Master | Master |
Phase | A | B | C |
Modbus ID | 1 | 2 | 3 |
If the settings are set as above and Grid Phase wrong occurs, LEAVE ALL CONNECTIONS THE SAME, but change the settings to the below:
| A | B | C |
Parallel | Yes | Yes | Yes |
Master or Slave | Master | Master | Master |
Phase | A | C | B |
Modbus ID | 1 | 3 | 2 |
This settings change allows the system to detect a change in phase rotation and clears the fault.
Was this article helpful?
That’s Great!
Thank you for your feedback
Sorry! We couldn't be helpful
Thank you for your feedback
Feedback sent
We appreciate your effort and will try to fix the article